TEL+44 (20) 8969 1367
FAX+44 (20) 8968 8913

admin@kaloricheater.co.uk
31-33 Beethoven Street
London W10 4LJ UK


:: CATALOGUE CONTENTS
compact portable
industrial fan heaters
portable fan
assisted heaters
4-20kW
unit heaters
uht unit
heaters
warm air curtains
and high level heaters
mayfair
convectors
forced air
consoles
panel
heaters
rectangular rod
type heater batteries
circular rod
type heater batteries
insertion
units
control
panels
tubular
heater units
immersion
heater units
electric
elements
ATEX, EExd
fan assisted unit
ATEX, EExd
convector heaters
ATEX, EExd cabinet
convector heaters
industrial finned
tubular heaters
halogen
heaters
ceramic
heaters
weather resistant
halogen heaters
halogen ceramic
and radiant heaters
heating
cables
heater
mats
under laminate
elements
? other products
and enquiries
   
 
   

B2 | uht unit heaters

APPLICATION

The UHT Blower Unit Heater is ideal for use where a higher capacity safe clean and dependable heating system is required It can be used in factories, workshops, sports halls, warehouses, for complete, auxiliary or frost protection heating. The UHT is a Space Heater, designed for heating high volumes of air by recirculation.

FEATURES OPTIONS

Heavy duty motor with built-in thermal overload protection

Stainless steel sheathed tubular elements (2-10kw) finned (15-25kW)

Auto reset over temperature safety cut-out

Safety fan guard

Directional horizontal louvres, individually adjustable for positive air flow control

Sturdy steel cabinet epoxy/polyester powder coated finished in ALMOND RAL R 9001

Automatic residual heat purge by fan overrun

Wall or celing mount bracket included

Integral thermostat sensing incoming air temperature

400v three phase, three wire units with or without 230v control circuit

Vertical mounting kit for chain suspension

Diffuser cones (for vertical discharge)

SELECTION

The UHT is designed to give a temperature rise across the heater of approximately 20°C thus achieving design temperature by recirculation. The installed kWs must be equivalent to the heat loss of the whole area to be heated. The UHT is not recommended for “spot” heating.

INSTALLATION

The heater should be mounted at a maximum height of 2.5m (2-10kw) or 3.0m (15-25kw) so positioned as to create an airflow around the airea. Wall or ceiling brackets are recommended. Electrical installation should be carried out by a qualified electrician to current regulations.

List
No.
Heater Rating Fan Motor Mounting Height
Max
Shipping Weight
Approx.
kg
kW Volt Phase Air Vol m3/h Watt r.p.m. Volt Phase Noise Level dbA
UHT3/1 3 230 1N 1180 25 1355 230 1 60 2.5 23
UHT3/3 3 400 3N 1180 25 1355 230 1 60 2.5 23
UHT5/1 5 230 1N 1180 25 1355 230 1 60 2.5 23
UHT5/3 5 400 3N 1180 25 1355 230 1 60 2.5 23
UHT7/3 7 400 3N 1180 25 1355 230 1 60 2.5 23
UHT10/3 10 400 3N 1180 25 1355 230 1 60 2.5 23
UHT15/3 15 400 3N 2220 80 1400 230 1 65 3.0 35
UHT20/3 20 400 3N 2220 80 1400 230 1 65 3.0 35
UHT25/3 25 400 3N 2220 80 1400 230 1 65 3.0 35

 

Dimensions (mm)

Size A B C D E F G H J
2-10kW 305 420 432 343 260 490 305 127 433
15-25kW 444 560 572 470 350 630 305 152 572


Optional Features

Suffix Part Code – Please Specify
C Integral conductor
T Integral thermostat
UHT-CD1 (2-10kW) Cone diffuser
UHT-CD2 (15-25kW) Cone diffuser
UHT-SK Threaded hooks for chain (4 per ki)

Standard three phase units require 3P+N supply

 

Design, specification, prices, etc. subject to alteration without notice